100-amp vs 200-amp service: do you actually need the upgrade?

Call (203) 680-9825

Request a free written estimate

Fill this out and the assigned contractor calls you back Mon-Fri 8-4 with a written estimate for your house.

Mon-Fri 8-4 callbacks · We do not sell your information · CT Lic. ELC.0200504-E1

Operated by AEQR.ai · Homes, businesses & light industrial *

Active fire, smoke, sparking or burning smell? Call 911. This form is not for emergencies.

No obligation · Texting optional, never required *

Prefer to call? (203) 680-9825. Answered any time by our automated assistant, which takes your details; a person calls back Mon-Fri 8-4. Calls may be recorded.

Short version. A 100A service gives you about 24,000 watts on paper and roughly 19,000 watts of comfortable continuous headroom; 200A gives 48,000 and about 38,000. If you are adding any two of heat pump, EV charger, induction range, hot tub or a second dryer/oven, the calculation almost always lands on 200A. If you only need more breaker spaces, a subpanel may be the cheaper fix.

What the numbers mean

Service amperage times 240 volts is the raw capacity: 100A × 240V = 24,000 W; 200A × 240V = 48,000 W. The 125% continuous-load rule means any load running three hours or more is sized at 125% of its rating, which is the same as saying such a load should not exceed 80% of the breaker feeding it. That is a rule about CONTINUOUS loads and their circuits — it is not a blanket reduction of the whole service to 80%. A load calculation adds continuous and non-continuous loads by their own rules, and it is the calculated demand, not a flat 80% figure, that is measured against 24,000 W or 48,000 W.

The NEC 220.82 calculation, without the jargon

Electricians size a dwelling service with the "optional method" in NEC §220.82. It is four lines:

  1. General lighting and receptacles: 3 VA per square foot of living space. A 2,400 sq ft colonial = 7,200 VA.
  2. Small-appliance and laundry circuits: 1,500 VA each; a typical kitchen has two plus one laundry = 4,500 VA.
  3. Fixed appliances at nameplate: range, oven, dryer, water heater, dishwasher, disposal, microwave, EV charger, hot tub — add them all up.
  4. Apply demand: 100% of the first 10,000 VA, 40% of everything after that. Then add the heating or air-conditioning load under NEC 220.82(C), which is not a flat 100% — it sets out several selections and you take the largest that applies. Central air or a heat pump counts at 100%; electric space heating counts at 65% where fewer than four separately controlled units are involved, and at 40% where there are four or more. Divide by 240 to get amps.

Worked example, using the optional method set out immediately above — not the standard method, which handles lighting differently. 39,700 VA of connected load. The first 10,000 VA counts at 100%, the remaining 29,700 VA at 40% — so 10,000 + 11,880 = 21,880 VA of demand, or about 91 A at 240 V. That fits a 100A service with roughly nine amps to spare, which is exactly why so many 1960s–1990s Fairfield County houses pass today and fail the moment an EV charger or heat pump is added.

What pushes a house over 100A

AdditionTypical circuitLoad in the calc
Level 2 EV charger, 48A60A, 240V11,520 VA at 48A × 240V; the 60A circuit comes from the 125% continuous-load rule (NEC 625.42)
Level 2 EV charger, 32A40A, 240V7,700 VA continuous
Cold-climate heat pump (3–4 ton) with backup strips30–60A8,000–15,000 VA (largest of heat/cool at 100%)
Induction range40–50A8,000–12,000 VA nameplate
Heat pump water heater30A4,500 VA
Hot tub40–60A (per nameplate)8,000–12,000 VA
Central AC, 3 ton30A~4,500 VA

Two of these on top of a normal all-electric kitchen and dryer is where the 100A math stops working. One of them, in a gas-heated house, often fits.

Which code applies in Connecticut right now

Connecticut enforces the 2022 State Building Code, which adopts the 2020 NEC (effective October 1, 2022). The 2026 code, adopting the 2023 NEC, was scheduled for July 1, 2026 and is delayed pending regulatory review as of the state's adoption page. Your electrician and town inspector work to whichever is in force on the permit date; the load calculation is the same under both.

Three honest outcomes

Ask the electrician to show the calculation. It's a one-page form; if they won't produce it, they're guessing.

Ready for a real number?

Planning ranges are not quotes. A licensed Connecticut electrician prices your panel after seeing it.

Request a free estimate →
Sources (checked 2026-09-10)
  1. NEC §220.82 optional dwelling calculation, explained (ExpertCE) — page dated 2025-11-28
  2. NEC §230.79(C) minimum 100A service, worked example (Dakota Prep) — page dated 2026-09-08
  3. What a 200-amp service can carry (Home Inspection Insider) — page dated 2024-02-04
  4. NEC §625.42 EV loads are continuous (text) — no date on page
  5. Eversource CT Electric Service FAQ — standard residential service is 200A — https://www.eversource.com/residential/about/doing-business-with-us/builders-contractors/electric-service-faq — no date on page
  6. Wilton CT — 2022 CT State Building Code (2020 NEC) effective Oct 1, 2022 — https://www.wiltonct.gov/building-department/pages/ct-state-building-code-information — no date on page
  7. CT DAS — code adoption process, 2026 code (2023 NEC) pending — https://portal.ct.gov/das/office-of-state-building-inspector/building-and-fire-code-adoption-process — no date on page

Published · Fairfield County, CT · Every figure above is sourced in the list above, with a date where the source publishes one.

Questions homeowners ask

Does the code require 200 amps?

No. NEC §230.79(C) sets a 100A minimum for a one-family dwelling. 200A is the practical standard because Eversource's standard residential service is 200A and because heat pumps, EV chargers and induction ranges each take a large share of a 100A service.

Can I add an EV charger to a 100-amp service?

Sometimes. A 48A charger draws 48A and needs a 60A circuit, because a continuous load is sized at 125%. The load is 48A; the circuit is 60A. On a 100A service that leaves little headroom once heat, range and dryer are counted. A load calculation decides it — or a load-management device that throttles the charger. Many Fairfield County homes with electric heat or a heat pump cannot.

What is the 80% rule people mention?

Continuous loads (three hours or more — EV charging is defined as continuous under NEC §625.42) are sized at 125% of the load, which is the same as saying a breaker should carry no more than 80% of its rating continuously. It is why a 40A charger needs a 50A circuit.

Disclosures

Who does the work. Work is performed by an independent licensed Connecticut electrical contractor · CT license ELC.0200504-E1 (verify at CT eLicense). ElectricalPanelUpgrade.net is an AEQR.ai network property and does not hold this contractor license; requests are routed to that independent contractor and provider assignment may change. Any contract and work are between you and the assigned contractor. License verified 2026-10-06. Contractor participation is by application only. Each contractor is personally vetted and interviewed by AEQR's owner, and exclusivity is earned, not purchased.

Text messaging (optional). The estimate form includes a separate SMS-consent checkbox. It is not pre-checked, and checking it is not required to submit a request or receive service. If you check it, you authorize Begolli of New York, LLC (operating as AEQR.ai, ElectricalPanelUpgrade.net) to send you text messages about your estimate request — confirmation, scheduling and follow-up. Message frequency varies (typically a few messages per request). Message & data rates may apply. Reply STOP to opt out at any time, or HELP for help. Consent is not a condition of any purchase. See our Privacy Policy (full SMS terms) and Terms of Use.

Pricing and scope. Planning ranges on this site cite dated sources (each guide lists them, with the date each was published) and are not quotes; every project is priced in writing after a site visit by a licensed contractor. Residential, commercial and light industrial electrical work in Fairfield County, CT. Your phone number goes to the one assigned contractor. We do not sell your information.